AEROSOL FIRE EXTINGUISHER
WITH ELECTRICAL ACTIVATION NAFEG
AFRAID
OF FIRE
OUR OTHER PRODUCTS
Unlike any other extinguishing agent, NAFEG condensed aerosol fire suppression technology interferes in the chain-reaction of the fire, leaving oxygen levels intact.
QUALITY AND SAFETY ARE IMPORTANT TO US
Application Industries
CNC-Machines • Control Rooms (sub Floor; Above Ceiling) • Electrical Cabinets • Engine & Compressors Rooms • Flammable and Combustible Liquids and Gases Storage • Paint Lockers • Marine Applications • 5 Server Rooms • Telecommunications Facilities
NO GLOBAL WARMING
LOW TOXICITY
HIGHLY EFFICIENT
MAIN FEATURES
NO OZONE DEPLETION
SMALL-SAFE-SIMPLE
APPROVED BY EPA FOR SNAP LISTING
COOL AND DRY; MAX. 10 YEARS STORAGE / SHELF LIFE
COST EFFECTIVE
IP67 PROTECTION CLASS
FOR A-B-C-E CLASS TOTAL FLOODING APPLICATIONS
OTHER NAFEG SIZES
FIRE CLASSIFICATION AND SUITABILITY
CLASS A
Combustible and flammable solid materials
Fully suitable
CLASS B
Flammable and incendiary liquids
Fully suitable
CLASS C
Flammable and incendiary gases
Fully suitable
CLASS E
Electrical equipment fires and fires due to electric current
Fully suitable
Description
NAFEG Aerosol Extinguisher, is designed to extinguish and defuse A type (solid fuel), B (liquid fuel), C (gas fuel) fires and E type (electricity) fires in enclosed volumes.
After the extinguishing agent amount is calculated for each fire type and the volume to be protected, solid NRE-CM agent within NAFEG cylinder and total number of NAFEG cylinders in the volume to be protected is determined. NAFEG-125 is designed to produce dry aerosol for extinguishing a fire in a 1,25 m3 enclosed volume. Aerosol extinguishers are compatible with standard sensors and control units and could be located inside of the protected volume,
Application
The NAFEG aerosols are recommended for the protection of large compartments against fire, such as storage rooms, archives, technical rooms and server rooms.
PROVIDING PREFERRED FIRE SUPPRESSION SYSTEMS
- Easy installation
Can be installed easily and quickly, into any environment.
- Low-maintenance
Our non-pressurized aerosol generators are 15 years maintenance free.
- Cost-efficient
There is no need for any expensive pipe-work or tank storage.
- Highly effective
Our systems are more effective than any other suppression medium.
- Eco-friendly
Aerosol is friendly for the environment and not harmful to humans or animals.
- Fully certified
NAFEG is certified according to numerous international standards.
OPERATION / DESCRIPTION
The NAFEG Aerosol Fire Extinguisher family is designed to extinguish and neutralize type A (solid fuel), B (liquid fuel), C (gas fuel) fires and type E (electric) fires in enclosed spaces. After calculating the required extinguishing agent concentration for each type of fire and the volume to be protected, and determining the appropriate NAFEG extinguisher for the volume, the solid NRECM agent in the NAFEG cylinder and the total number of NAFEG cylinders in the area to be protected are determined. NAFEG Aerosol Extinguishers offer solutions for every need with electrical, mechanical and both electrical and mechanical activation options.
Electrically Activated NAFEG: NAFEG Electrically Activated Aerosol Fire Extinguisher; It communicates with the control box via the military connector on it and is activated by the fire signal sent to the control box by the UVIR/Thermal Fire Detectors produced by NERO Industry. It can also be controlled remotely by providing manual activation when necessary.
TECHNICAL SPECIFICATIONS
SPECIFICATIONS | NAFEG-125 | NAFEG-250 | NAFEG-500 |
---|---|---|---|
PRODUCT CODE | NE-Z-1125 | NE-Z-1250 | NE-Z-1500 |
Extinguishing Volume | 1,25 m³ | 2,50 m³ | 5,00 m³ |
Activation Mode | Electric | ||
Discharge Time | 4-6 sec | ||
Discharge Distance | 2m | ||
Activation | 1.2 A – 24V DC | ||
Operating temperature | -40°C (-104°F) – 120°C (248°F) | ||
Power Requirement | 1.2A @ 3 milliseconds | ||
Dimensions(mm) | Ø 88 H 132 | 88 H 202 | 88 H 295 |
Weight(g) ± 10 | 1500 | 2200 | 3100 |
Extinguishing Volume(m³) | 1.25 | 2.5 | 5 |
Protection Level | IP67(optional) |
SPECIFICATIONS | NAFEG-125 | NAFEG-250 | NAFEG-500 |
---|---|---|---|
PRODUCT CODE | NE-Z-1125 | NE-Z-1250 | NE-Z-1500 |
Extinguishing Volume | 1,25 m³ | 2,50 m³ | 5,00 m³ |
Activation Mode | Electric | ||
Discharge Time | 4-6 sec | ||
Discharge Distance | 2m | ||
Activation | 1.2 A – 24V DC | ||
Operating temperature | -40°C (-104°F) – 120°C (248°F) | ||
Power Requirement | 1.2A @ 3 milliseconds | ||
Dimensions(mm) | Ø 88 H 132 | 88 H 202 | 88 H 295 |
Weight(g) ± 10 | 1500 | 2200 | 3100 |
Extinguishing Volume(m³) | 1.25 | 2.5 | 5 |
Protection Level | IP67(optional) |
For over 25 years we offer exceptional fire extinguishing aerosol generators. Our customers all around the world trust our aerosol fire suppression systems for numerous reasons.